K3030i

Universal Protection Relay Test Set

High precision and powerful 3-phase relay test set and commissioning tool;
Power & Accuracy in one single PACKAGE, 3x35A, 4x310V analog outputs;
The ever-expanding test library templates;

Description

● Universal Relay Test Applications
● 7 Channels (3x35A & 4x310V) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 60x harmonics.
● Variable battery simulator, DC 0-350V, 140Watts max.
● Transient play back up to 3KHz
● Fully function KRT software testing modules
● Graphical test modules and templates for testing of various relays
● Quick relay testing facility in Manual mode
● Shot/Search/Check, Point & Click testing
● RIO/XRIO import & export facility
● Switch on to fault test(SOTF)
● Power system model for dynamic testing
● Online Vector display
● Automatic test results assume
● Automatic test report creation
● Inbuilt GPS sync end-to-end testing
● Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection
● 3-Years guarantee of free repair and life-long maintenance
● Lightweight, <19.5Kg
● Free software upgrade

Specifications

Voltage Outputs
Output Range & Power 4×310 V ac (L-N) 124 VA max each
3×350 V dc (L-N) 140 W max each
Accuracy ±2mV @ <2V ac
<0.015%Rd+0.005Rg Typ. @ 2~310V ac
<0.04%Rd+0.01Rg Guar. @ 2~310V ac
±10mV @ <5V dc
±0.5% @ ≥5V dc
Voltage Range Range I : 30V
Range II : 310V
Automatic Range
DC Offset <10mV Typ./ <60mV Guar
Resolution 1mV
Distortion <0.015%Typ. / <0.05% Guar.
Current Outputs
Output Range & Power 3×35A ac (L-N) 450 VA max each
1×100A ac (6L-N) 1200 VA max
3×20A dc (L-N) 300W max each
Accuracy ±1mA @ <0.5A ac
<0.02%Rd+0.01Rg Typ. @ 0.5A~35A ac
<0.05%Rd+0.02Rg Guar. @ 0.5A~35A ac
±5mA @ <1A dc
±0.5% @ ≥1A dc
Current Range Range I: 3A
Range II: 35A
Automatic Range
DC Offset <3mA Typ./ <10mA Guar
Resolution 1mA
Distortion <0.025%Typ. / <0.07% Guar.
Frequency & Phase Angle
Frequency Range DC~1KHz, 3KHz transient
Frequency Accuracy ±0.5ppm
Frequency Resolution 0.001 Hz
Phase Range -360°~360°
Phase Accuracy <0.02° Typ. / <0.1° Guar. 50/60Hz
Phase Resolution 0.001°
Aux. DC Voltage Source (Battery simulator)
Range 0~350V @ 140W max
Accuracy 0.5%Rg Guar.
Binary Input
Quantity 8pairs
Type wet/dry, up to 300Vdc max input
Time resolution 10us
Sampling Rate 10KHz
Debounce time 0~25ms (Software Controlled)
Time range Infinite
Time errors ±1ms @ ≤1s, ±0.1% @ >1s
Galvanic isolation Isolated each pairs
Binary Output (Relay Type)
Quantity 4pairs
Type Potential free relay contacts, software controlled
Break Capacity AC Vmax: 400Vac / Imax:8A / Pmax:2500VA
Break Capacity DC Vmax: 300Vdc / Imax:5A / Pmax:150W
Binary Output (Semiconductor Type)
Quantity 4pairs
Type: Open-collector, Combination type male
Break Capacity DC 5~15Vdc / 5mA, 10mA max
Response time: 100us
Synchronization
Synchronization Mode GPS, SMA type antenna connector
Power supply & Environment
Nominal Input Voltage 110V/220/230V ac, Appointed
Permissible Input Voltage 85~264Vac, 125~350VDC, auto-protective
Nominal Frequency 50/60Hz
Permissible Frequency 45Hz~65Hz
Power Consumption 1500 VA max
Connection Type Standard AC socket 60320
Operating Temperature -10℃~55℃
Storage Temperature -20℃~70℃
Humidity <95%RH, non-condensing
Others
PC Connection RJ45 Ethernet, 10/100M
Grounding Terminal 4mm banana socket
Weight 19.5 Kg
Dimensions(W x D x H) 360×450×140(mm) 

Documents à télécharger

Fiche Technique